Controls and Safety : Humidistats
  >  
Type Q7B
Type Q7B
Wall mounting miniature humidistat
Controls and Safety
Humidistats
Check PDF
Click to see more languages available in the datasheet
Product applicable fields
    The product does not currently have its own area
product presentation

MAIN FEATURES

Main Application: This humidistat is designed for indoor application to switch on a heater or a ventilating fan It can also be used to switch on humidifiers, dehumidifiers, or other devices. It must be vertically wall mounted in a ventilated area.

Humidity sensing element: hygroscopic polymer film with special treatment, produced by Ultimheat, ensuring a fast response, long life and high stability

Setting range: 35 to 95% RH

Measuring accuracy: ±5% RH

Differential at 50% RH: 8% RH (±3% RH )

Measuring medium: air, pressure-less, non-aggressive

Electrical contact: silver contacts, SPDT, 5A 250V

Connection: 3 screw terminals for 1.5mm² wires, max torque 0.5Nm

Mounting: wall mounting, with 2 screws dia 4mm max, distance 31 x 51mm

Operating temperature: 0 to+60°C (+32 to +140°F)

Storage temperature: -20 to +70°C (-4 to +158°F)
Mounting position: vertical

Voltage supply: the humidistat should be mounted such that there is no buildup of condensate on or in the device. If the voltage supply is higher than 48V there is a risk of voltage arcing in the event of water  condensation on the micro-switch or connecting terminals which might destroy the control.

Ingress protection class: IP30

Dimension: 67x50x29mm

Maintenance: The humidity sensing ribbon is maintenance-free in  clean air. Air containing solvent can cause measuring errors and failure, depending on the type and concentration. Deposits such as resin  aerosols, lacquer aerosols, smokes, which eventually form a water-repellent film are harmful for the measuring element.