Controls and Safety : Manual Reset Thermostat
  >  
Type 8X
Type 8X
DPNC manual reset high limit, fail safe
Controls and Safety
Manual Reset Thermostat
Check PDF
Click to see more languages available in the datasheet
Product applicable fields
    The product does not currently have its own area
product presentation

Housing dimensions: 43 × 35 × 29mm (without terminals and diaphragm).

Capillary: Copper, capillary length 250mm or 900mm, 150mm long PVC sleeve on capillary. Capillary minimum bending radius 5mm.For technical reasons, we do not recommend to use capillary length longer than 900mm

Bulb: Copper, corkscrew type for temperatures from 60 to 130°C(140 to 266°F), tubular dia 6mm from 130°C to 170°C(266 to 338°F)

Temperature sensing element: Liquid-filled thermostatic assembly whose boiling causes tripping of the contact. Therefore, unlike liquid filled systems, these thermostats are sensitive to atmospheric pressure, and their reaction time is slower

Terminals: 6.35 × 0.8 quick connect terminals.

Adjustment: Fixed setting.

Manual reset: Fail safe action, front access button

Mounting: Front bushing, with M10 × 1.

Rating: 20A 250VAC

Contacts: DPST (snap action contact)

Max ambient temperature on head: 125°C (257°F)