中文
English
Home
Applications
Products
Certification
About Us
Contact
Home
  >  
Controls and Safety : Automatic Thermostat
  >  
Type Y261
Type Y261
3 parallel ways connection box for heat tracing cables, with built-in antifreeze thermostat
Controls and Safety
Automatic Thermostat
Check PDF
Click to see more languages available in the datasheet
Product applicable fields
  • Air and Fluid heating solutions
  • Renewable energy
  • Industry
  • Ventilation
  • Petrochemistry
product presentation

Applications
This box allows to connect, with a good IP65 ingress protection, 2 rounds or flat heating cable to a round power cable or providing at the same time the continuity of the power line.

The built-in disc thermostat provides the anti-freeze function.

It can be mounted on a flat surface, or on a pipe.

Terminals positions provide easy access, wiring is simple, including for braided heating cables.

Compatible with all types of flexible heating wires, round or flat.

                                                                                                   Main features
Material: Polyamide 66 black, 90mm x 67mm x 36mm (Cable glands not included). Excellent UV resistance.

Waterproof grade: IP65
Thermostat: rating 16A 230V, open by temperature rise at 10°C +/-3°C, close at 4°C+/-3°C (Other temperatures on request)
Mounting: 2 removable wall mounting bracket, holes distance 96mm. Pipe mounting with cable tie also possible, by using the 2 rings located on the side of the box
Terminals:
- Screw terminals with captive toothed square washers accepting rigid or flexible conductors.

- The mechanical tightening of the cable is ensured by a screwed metal saddle, usable on round or flat cable. This patented saddle also ensures the earthing of the metal braid of the heating cables.

- Wire gauge: 3 x 1 mm² to 3 x 2.5mm²
- Maximum permissible intensity: 16A 250V
Cables outlet: with M24 cable glands, with 70 shore NBR gaskets (Silicone is available on request).

- Maximum diameter of round cables: 8; 12 or 14 mm depending on the gaskets installed.

- Limit sizes of oblong cables:
- from 8 x 5 to 9.5 x 6 mm
- from 9.5 x 2.5 to 11 x 3.5 mm
- from 11 x 4 to 13 x 6mm
- from 12.5 x 8 to 14.2 x 9.2mm
For more information about tightening possibilities on round and oblong cables, see the catalogue page on 6YTP cable glands.

Safety sealing: supplied with 5 red plastic ties for use in the sealing holes
Easy assembly: Assembly is made with full access to terminals when cover is removed. Mounting on wall or pipe can be made with cover removed or cover assembled.

Accessories: Stainless steel bracket for mounting distant from the pipe, see accessories page 6YTQT.

Options: Model for 3 heating wires without power supply cable and model for one heating wire and 2 power supply cables.