Applications
- Indoor mounting, in a box or a cabinet with Din rail, for control of frost protection and electrical tracing systems. (Defrosting and snow removal of gutters, roofs, heated parking ramps).
This electronic temperature controller with the simplest and the most instinctive setting by end user was designed for easy incorporation inside cabinets with DIN rail mounting. It can be used by untrained operators.
It provides simple On Off action temperature control.
It is possible to set °C or °F display, heating or cooling relay output, decimal display, sensor type and temperature range by internal Dip switches (Without access by end user).
End user has access to set point and differential setting only.
Adjustment of maximum temperature can be set without need to open the control.
Technical features
Dimensions: 86.9 x 58 x 52.5mm
Display: 3+1 digits, LED. The fourth digit is used to display °C or °F, upon setting made.
Set point setting: In normal use, the display shows the measured temperature. Push “+” or “-” keys will display the set point value, and at that time it can be adjusted with “+” and “-” keys. No action during 5 seconds will register the new set point value and bring back display to measured value.
Temperature differential setting: In normal use, the display shows the measured temperature. Push “D” key will display the differential value, at that time it can be adjusted with “+” and “-” keys. Push “D” again or no action during 5 seconds will register the new differential value and bring back display to the measured value.
Action: On-Off
Temperature sensor: Pt100 (2 or 3 wires) or NTC 10Kohms @25°C, B= 3380 (2 wires) Temperature sensor can be selected by a dip switch on circuit (No access to final user)
Accuracy: +/-1% of scale
Temperature adjustment ranges:
-30+120°C (-20+250°F), with 1° display
-30,0 to +40,0°C (-20,0 + 99,9°F), with 1/10° display
-30+400°C (-20+750°F), with 1° display
Temperature range and decimal digit can be selected by a dip switch on circuit (No access to final user).
Power supply: 90 to 240V, 50Hz or 60Hz.
Relay output: SPNO when there is no power supply, 16A 250V res., 100,000 cycles. Output Led displays relay position Relay action: Heating or cooling, open or close on temperature rise output relay action can be selected by a dip switch on circuit (No access to final user)
°C or °F display: can be selected by a dip switch on circuit (No access to final user).
Maximum possible set point adjustment by user: Push “D” button more than 10 seconds, display shows the maximum temperature that can be set by the user. Then it is possible to adjust this value with “+” and “-“. Push again on “D” or do nothing during 5 seconds will register the maximum possible setting value and control will come back to the measured value.
Ambient: -20+60°C, 10-90% RH
Power: <4W
Fail safe safety:
- If no power supply, relay output contact will open
- If Pt100 sensor or NTC is broken or not connected properly, relay output contact will open and display will show “EEE”- If measured temperature is higher than allowed by the set range, display will show HHH
- If measured temperature is lower than -30.0°C or -20.0°F, display will show LLL
Electrical connections:
- Power input: Neutral, phase, ground, with 2.5mm² terminals
- Power output: Neutral, phase, ground, with 2.5mm² terminals for direct connection to the load.
- Temperature sensor: three 2.5mm² screw terminal
One removable jumper provides a potential free relay output for applications needing a separate circuit for relay, external timer or other.
Internal parameter settings: Process is given on request to approved distributors. This allows to store only one product and set parameters upon end user request.
Options: Waterproof wall mounting box
Standards: CE certificate by TUV, and ROHS and Reach components.