Heating Equipment : Fan Heaters
  >  
Type 9PF
Type 9PF
Commercial and industrial convection radiators Cabinet fan heaters, range from 50 to 400W
Heating Equipment
Fan Heaters
Check PDF
Click to see more languages available in the datasheet
Product applicable fields
    The product does not currently have its own area
product presentation

Typical Applications:
Heavy duty fan heating in Traffic Signal Control Boxes, Automatic Teller Machines, Outdoor Electrical Power Enclosures, Control Panels, Control Valve Housings, Switch Gear, Clothing Lockers and Railway station lockers.

Operation: Temperature differences in cabinets, mostly in outdoor applications, often result in humidity and condensation which may cause function failures and corrosion. The use of the appropriate heating unit inside the cabinet will eliminate these problems.

Simply keep the cabinet temperature above the outer temperature (thermostat controlled models), or a humidity level below 50% (Humidistats controlled models). It also happens that the very low external temperature dips below the minimally acceptable ranges for electronics or other components. In this case the heaters are used to bring the internal temperature of the cabinet above the limit. The fan distribute the internal warm air equally throughout the control cabinet
Compared to PTC heaters, sheathed tubular heaters deliver unsurpassed strength, a power invariable in time, they do not age and do not drift, and do not produce huge peak starting current.

The metal casing provides increased mechanical protection and the best heat resistance.

Main features
Heating Element: 8mm diameter, 304L sheathed stainless steel heater. Other features of these elements (Humidity resistance, insulation etc…) see P3 of section 4.

Heater surface load: 0.5w/cm² (2.2W/in²) or 1w/cm² (6.5W/in²) to avoid overheating.

Case Material: Electro-galvanized steel or 304 stainless steel according to models.

Manual reset temperature safety cut-out: Set at 70°C (158°F) to protect against over-heating in case of fan failure, or obstructed air flow inlet

Setting range: 4°C to 40°C (40 to 105°F) for adjustable models. 40°C(105°F) for fixed setting models

Fan: 120 × 120mm, air flow: 100m³/h. L10 life expectancy: 50,000 h (>5 years) at 25°C. L10 refers to the time at which statistically, 90% of the fan will still be operative. Life expectancy is reduced by about 50% when ambient temperature rises to 50-70°C

Control lamp: Illuminated when heating is on (on model 9PF3)

Operating voltage: 220-240V AC, 50/60Hz, (100-120V AC on request).

Operating temperature: -45 to +70°C. Max 90% RH.

Ingress protection: IP 20
Electrical connection: By screw locking connector (cord with connector, 2 meters, H05VVF 3 × 0.75mm² supplied) Mounting: Two screws, 130 to 140mm distance. We recommend installing heaters in the lower part of the cabinets, which is usually the coldest area, with ventilation blowing up, to produce optimal air circulation.

Option: Mounting clips for 35mm DIN rail. (EN60715).

Accessories:
- See P5-P6 of section 8, Din rail mounting remote thermostats and humidistat used in cabinet heaters.

- See section 2 of this catalog tables providing heaters power selection vs temperature and cabinet sizes.

(Add additional 50% to the determined power if the cabinet must be located in windy conditions)