Type 5EE, 5EJ, 5EN, 5EA
Type 5EE, 5EJ, 5EN, 5EA
Eutectic alloys fusible links for medium loads
Controls and Safety
Fire and Damper Mechanisms
Check PDF
Click to see more languages available in the datasheet
Product applicable fields
  • Industry
  • Ventilation
  • Professionnal kitchen
  • Fire Systems
product presentation

Material: Brass
Surface Protection: No special surface protection.

ROHS compliance: These fusible links are available in two versions.

- Non-ROHS compliant, using traditional alloys containing lead and cadmium, for temperatures 68°C (155°F); 72°C (162°F); 96°C (205°F); 103°C (218°F); 120°C (248°F).- ROHS compliant, using ternary alloys based on bismuth, tin and indium, (the high cost of indium makes these models 2 to 3 times more expensive than non-Rohs types) for temperatures 60°C (140°F); 72°C (162°F); 79°C (174°F); 109°C (228°F); 117°C (242°F).

Identification: Model, temperature in °C and date of manufacture are stamped on each fusible link.

Tests:
- Mechanical resistance at ambient temperature: 100% in production.

- Trip temperature under static load: by statistical sampling.

- Trip time in temperature rise under load according to ISO 10294-4: by statistical sampling.

- Holding load 1h at 60°C or 90°C: compliant and verified by statistical sampling in production (Test according to ISO 10294-4).

- Triggering under minimum load: compliant and verified by statistical sampling in production (Test according to UL33)
Salt spray resistance: According to ISO9227-2012, subjected to a mist formed of 20% by weight of sodium chloride in distilled water, at 35°C for 5 days (120h), the fusible links retain their aptitude for the function, in the response times specified by the standard.