MUSEUM
Home
  >  
Controls and Safety : Fire and Damper Mechanisms
  >  
Type 5E2, 5E3, 5E4,5E5, 5E6
Type 5E2, 5E3, 5E4,5E5, 5E6
Type 5E2, 5E3, 5E4,5E5, 5E6
Miniature fusible links, for kitchen ventilation and hoods for home and professional equipment
Controls and Safety
Fire and Damper Mechanisms
Check PDF
Click to see more languages available in the datasheet
Product applicable fields
  • Industry
  • Ventilation
  • Professionnal kitchen
  • Fire Systems
product presentation

Manufactured in a fully automated way, these fire detection fuses are particularly economical for domestic applications in mechanical ventilation, extractor hoods. They are also externally coated with an alloy protecting them from corrosion.

Material: Brass (possible realization in red copper if shorter response times are required).

Surface Protection: Eutectic alloy.

ROHS compliance: These fusible links are available in two versions.

- Non-ROHS compliant, using traditional alloys containing lead and cadmium, for temperatures 68°C (155°F); 72°C (162°F); 96°C (205°F); 103°C (218°F); 120°C (248°F).

- ROHS compliant, using ternary alloys based on bismuth, tin and indium, (the high cost of indium makes these models 2 to 3 times more expensive than the previous ones) for temperatures 60°C (140°F); 72°C (162°F); 79°C (174°F); 109°C (228°F); 117°C (242°F).

Identification: Model, temperature in °C and date of manufacture are printed on each fusible link.

Tests:
- Mechanical resistance at ambient temperature: 100% in production.
- Trip temperature under static load: by statistical sampling.
- Trip time in temperature rise under load according to ISO 10294-4: by statistical sampling.
- Holding load 1h at 60°C or 90°C: compliant and verified by statistical sampling in production (Test according to ISO 10294-4).
- Triggering under minimum load: compliant and verified by statistical sampling in production (Test according to UL33).

Salt spray resistance: According to ISO9227-2012, subjected to a mist formed of 20% by weight of sodium chloride in distilled water, at 35°C for 5 days (120h), the apparatuses retain their aptitude for the function, in the response times specified by the standard.

Type 5E2 5E3 5E4 5E5 5E6
Welding surface (mm²) 84 mm² 159 mm² 224 mm²  258 mm²  80 mm²
Maximum permissible permanent load * (DaN) 8.5 DaN 16 DaN  22 DaN 26 DaN  8 DaN
Minimum breaking load  2N 4N  4N  4N  3N 
Response time according to ISO 10294-4 under maximum load ** 2min 43 sec 2min 46 sec 2min 51sec  2min 51sec  2min 38sec

* Maximum permanent load depends on alloy composition and ambient temperature. Values are given for guidance only, and for a 72°C non ROHS eutectic alloy. Alloys with temperatures below 72°C and those that are RoHS compliant, generally have a high proportion of Indium, which greatly reduces the mechanical strength.
** Values measured in our own testing equipment. Testing conditions and equipment comply with ISO10294-4 and ISO DIS 21925-1 2017, fig. C1