Type 8Z
Type 8Z
Type 8Z
1, 2, 3-pole manual reset limiter. Fixed setting. Comply with IEC 60079-0, IEC 60079-15. To use when R290 highly flammable refrigerant classed A3 upon ISO 817 may be present. This is not a Ex certified product. Maximum rating 20 (3.3)A 250V, 16(2.6)A 400V Waterproof. Calibration from 70°C to 130°C
Controls and Safety
Explosion-proof
Check PDF
Click to see more languages available in the datasheet
Product applicable fields
    The product does not currently have its own area
product presentation

Main applications
General rules for installation:
Important note: Fully compliant for heat pumps and water heater heat pumps using R290 refrigerant according to EN60335-2-40 (Particular requirements for electrical heat pumps) – Arcs and sparks protection chapter.

General description:

This Thermal Cut Out was designed as a sealed device as per lEC 60079-15:2017.
The Thermal Cut Out met the requirements of lEC 60079-15: 2017 clause 9.
The Thermal Cut Out was examined and tested according to clause 26.5.1.2 of lEC 60079-0: 2017 and clause 11.2 of lEC 60079-15: 2017.
The Thermal Cut Out passed the test items, complies with the relevant clauses of lEC 60079-15: 2017 cited by lEC 60335-2-40: 2024 and UL 60335-2-40: 2022, applicable to appliance with A3 refrigerants.

Certification:

- UL: UL 60730-1, UL 60730-2-9, CAN/CSA E60730-1:15, UL/CSA E60730-2-9 (6,000 cycles)
- CE: LVD certified by TÜV, EN60730-1, EN60730-2-9 (6,000 cycles)
- Explosive atmosphere by TÜV according to standards and specific chapters above.
Registration No.: CL 50710811 0001

Technical features

Housing dimensions: see drawings

Capillary: Copper, capillary length 250mm, 500 or 900 mm. Black PVC sleeve on capillary. Capillary minimum bending radius 5 mm.
For technical reasons, we do not recommend to use capillary length longer than 900 mm. We don’t recommend 250mm long capillary for calibration temperature above 90°C (194°F)
Special lengths on request.

Bulb: Copper, corkscrew type for temperatures from 70 to 130°C (158 to 266°F).
Straight uncoiled capillary available on request

Temperature sensing element: Liquid-filled thermostatic assembly whose boiling causes tripping of the contact.
Therefore, unlike liquid filled systems, these thermostats are sensitive to atmospheric pressure, and their reaction time is faster.

Terminals: Six 6.35 × 0.8 quick connect terminals, or 6 M4 input screw terminals with saddle. (Other terminals combinations are possible). Terminals can be horizontal or vertical

Adjustment: Fixed setting

Mounting: Front bushing, with M10 × 1 thread

Manual reset: Fail safe action, front access button

Contacts: 3 poles single throw 20(3.3)A 250V, 16(2.6)A 400V snap action contact. Single pole and double pole available with same dimensions.

Max ambient temperature on head: 85°C (185°F). Must not be higher than calibration temperature -10°C (-18°F).

Acceptable degree of pollution for use in 250V: 3

Acceptable degree of pollution for use in 400V: 2